Installation
2–4 975-0298-01-01
Table 2-1 contains the arrangements of wire colors to pin numbers for the
T568A standard.
• Network terminators (Figure 2-3)—the Xanbus network must be
properly terminated at each end with male or female network
terminators to ensure the communication signal quality on the
network. If the network is not properly terminated, signal quality is
degraded and performance on the network is reduced. Permanent
configuration without terminators is not supported by Xantrex. The
System Control Panel ships with one male terminator already
installed. Depending on your network layout, this terminator may
need to be removed and inserted into another device elsewhere in the
network.
Figure 2-1
T568A Standard Wiring
Pin Number Conductor Name CAT 5 Cable Insulation Color CAT 5e Cable Insulation Color
1 NET_S White/Green White/Orange
2 NET_S Green Orange
3 NET_C White/Orange White/Green
4 CAN_L Blue Blue
5 CAN_H White/Blue White/Blue
6 NET_C Orange Green
7 NET_S White/Brown White/Brown
8 NET_C Brown Brown
Figure 2-2
RJ-45 Connector
Pins:
8 7 6 5 4 3 2 1