Troubleshooting
5–2 975-0298-01-01
Troubleshooting Reference
Types of Faults and Warnings
The various types of fault and warning messages behave differently, and
give you the option to treat them differently when they appear. For more
information about the types of fault and warning messages, see “Types”
on page 4–4 and “Types of fault messages” on page 4–7.
Warning Reference Table
Table 5-1
Warning Reference Table
Warning
number Message Type Cause Action
W250 The value failed to
change. Try again.
Automatic A Xanbus-enabled device
rejected the new setting.
A temporary communication
problem stopped the System
Control Panel changing a
value that you entered.
Check device operation
guide and settings. The
setting may be out of
range, the system mode
may be incorrect, or
another device setting is
overriding the setting you
want to change.
Try changing the value
again.
W251 Please confirm:
Equalization
process.
Manual You have enabled
Equalization on the inverter/
charger or charge controller
menu.
Press Enter to begin
equalizing batteries or Exit
to return to the previous
menu.
W252 Please confirm:
Restore default
settings.
Manual You have selected the
Restore Defaults command.
Press Enter to restore
default settings or Exit to
cancel.
W254 The value failed to
change. Try again.
Manual The setting you are changing
can only be changed when
the system is in Standby
mode.
Put the system in Standby
mode, change the setting,
then return the system to
Operating mode.