Troubleshooting Reference
975-0298-01-01 5–3
W255 System clock not
set. Set correct time.
Manual On initial startup, the clock
needs to be set. The system
will not operate correctly
until it is.
Set the clock to the correct
time. See “Using the Clock
Menu” on page 3–10.
W256 A device is lost.
Check connection.
Manual The System Control Panel
has lost communications
with another device on the
network.
Check network connection
between the System
Control Panel and the
device.
W257 New device
detected.
Check device
settings.
Manual You have connected a new
device to the network or
reconnected a disconnected
device.
Acknowledge the message
and check that the device is
properly configured.
W258 Device instance
is duplicated.
Manual Two networked devices of
the same type have the same
instance.
Select a different instance
ID on one of the devices’
Setup menu.
W501 SCP has fixed a
memory problem,
restored defaults.
Manual The System Control Panel
encountered an internal
memory problem upon
startup. To remain
operational, the System
Control Panel restored its
default settings.
Acknowledge the warning
and reset configurable
settings if necessary.
W502 Not reporting;
Info may be
missing.
Manual
Table 5-1
Warning Reference Table
Warning
number Message Type Cause Action