94
When the frequency source is used as the main and auxiliary operation, P0-09 is used as the bias frequency, and
the superposition of the main and auxiliary operation results is used as the final frequency setting value, which
makes the frequency setting more flexible
0.00Hz~max output frequency (P0-13)
When the frequency input channel is set to digital setting, the parameter value is the initial value of frequency
digital setting.
Frequency shutdown memory selection
for digital setting
Memory and no memory refers to the frequency adjustment by keyboard and key (or up and down of X
terminal) during operation, and whether the changed frequency is memorized during shutdown. When no
memory is selected, the frequency will return to the set value of P0-10 (preset frequency) after shutdown.
Note: When memory is selected, it is only applicable to normal shutdown. If power is cut off suddenly during
operation, the frequency will not be memorized after power is turned on again.
Used to set the maximum output frequency of frequency converter.
Upper limit frequency source
The default upper limit frequency is set by P0-15. It can also be set by analog quantity (AI1, AI2, AI3), pulse
and communication. When the operating frequency reaches the upper limit frequency, the upper limit frequency
will be maintained. Set the upper limit through analog quantity and pulse, please refer to P2-01~P2-70.
Lower limit frequency P0-17~ max output
frequency P0-13
Set the upper limit frequency, the setting range is from lower limit frequency P0-17 to max output frequency
P0-13.
Upper limit frequency offset
0.00Hz~max output frequency (P0-13)
When the upper limit frequency source P0-14 is set to analog or pulse setting, P0-16 is used as the offset of the
set value, the offset frequency is added with the upper limit frequency value set by P0-14 to get the set value of
the final upper limit frequency.
For example: the operation frequency is given as P0-10 = 30, P0-14 = 4 (pulse setting), P0-16 = 10. At this time,
if the pulse frequency is not given, the inverter can only run to 10Hz. If the pulse frequency is given to 25Hz,
the upper limit frequency is P0-16 + P0-14 (pulse) = 10 + 25 = 35Hz, it can run to the preset frequency 30Hz.