101
defined by (PF-00). If the terminal is valid, it will be switched to
another mode. During operation, it can be switched through the
terminal, and the switch will take effect immediately
PID is temporarily invalid, the inverter maintains the current output
frequency, and no longer adjusts the PID of frequency source.
Reverse action direction of
PID
When the terminal is effective, the PID function reverses
When the terminal is valid, the integral regulation function of PID is
suspended, but the proportional regulation and differential regulation
function of PID are still valid.
When the PID parameter switching condition is terminal X (PA-13),
and the terminal is invalid, the PID parameters use PA-10 ~ PA-12;
When the terminal is valid, PA-16 ~ PA-18 are used.
External fault normally ON
input
When the signal is sent to the frequency converter, the frequency
converter will report the fault Err43 and deal with the fault according
to the action mode of fault protection (see function code P7-46 for
details).
External fault normally close
input
When the normally closed signal of external fault is sent to the
inverter, the inverter reports the fault err43 and stops.
When user defined fault 1 and 2 are valid, the frequency converter
alarms Err48 and Err49 respectively. The frequency converter will
handle according to the action mode selected by fault protection
action selection (P7-47).
Motor parameter selection
terminal
Two groups of motor parameters can be switched through the two
states of terminals.
Switching between main
frequency source A and preset
frequency
If the terminal is valid, frequency source A is replaced by preset
frequency (P0-10)
Switching between main
frequency source B and preset
frequency
If the terminal is valid, frequency source B is replaced by preset
frequency (P0-10)
Frequency setting active
terminal
When the terminal is valid, it is allowed to modify the frequency; If
it is invalid, it is forbidden to modify the frequency
When the terminal is valid, the inverter will switch to DC braking
state directly
When the terminal is effective, the frequency converter first
decelerates to the starting frequency of DC braking, and then
switches to the DC braking state.
When the terminal is effective, the inverter stops at the fastest speed,
and the current is in the upper limit of the set current during the stop
process. This function is used to meet the needs of the inverter to
stop as soon as possible when the system is in emergency.
When keyboard control, the terminal can be used to stop the inverter,
which is equivalent to the function of stop key on the keyboard