107
Parameter
Name
Range
P2-37
AI curve 4 max input corresponding
setting
-100.0% ~ +100.0%
P2-38
AI curve 5 min input
-10.00V ~ P2-40
P2-39
AI curve 5 minimum input
corresponding setting
-100.0% ~ +100.0%
P2-40
AI curve 5 inflection point 1 input
P2-38 ~ P2-42
P2-41
AI curve 5 inflection point 1 input
corresponding setting
-100.0% ~ +100.0%
P2-42
AI curve 5 inflection point 2 input
P2-40 ~ P2-44
P2-43
AI curve 5 inflection point 2 input
corresponding setting
-100.0% ~ +100.0%
P2-44
AI curve 5 max input
P2-42 ~ +10.00V
P2-45
AI curve 5 max input corresponding
setting
-100.0% ~ +100.0%
Curve 4 is determined by four points, which is more flexible.
The voltage/current should meet the requirement: AI min input (P2-30) AI curve inflection point 1 input
(P2-32) AI curve inflection point 2 input (P2-34) AI max input (P2-36).
Curve 5 please refer to the explanation of curve 4.
Parameter
Name
Range
P2-54
AI curve selection
Ones bit
AI1 curve selection
1
Curve 1 (2 points, refer to P2-18~P2-21)
2
Curve 2 (2 points, refer to P2-22~P2-25)
3
Curve 3 (2 points, refer to P2-26~P2-29)
4
Curve 4 (4 points, refer to P2-30~P2-37)
5
Curve 5 (4 points, refer to P2-38~P2-45)
Tens bit
AI2 curve selection, ditto
Hundreds bit
AI3 curve selection, ditto
Curve 1, curve 2 and curve 3 are linear relations determined by two coordinate points; Curve 4 and curve 5 are
broken line relations determined by four coordinate points.

Table of Contents