111
Lower frequency arrival
(operation related)
When the operating frequency reaches the lower frequency,
the ON signal is output. The signal is off in the shutdown
state.
Fault output (free shutdown fault
and no output when under
voltage)
Fault of free shutdown and no output when under voltage.
Module temperature arrival
When the inverter module radiator temperature (P8-19)
reaches the set module temperature (PC-47), the ON signal
is output
Fault output (output only after
fault shutdown)
When the frequency converter fails, and the fault
processing mode is continue to run, the frequency converter
alarm output.
Motor over temperature alarm
Motor temperature acquisition value is greater than P7-37
value, alarm output
When the inverter is in reverse operation, it outputs ON
signal.
Software overcurrent output
Current detection arrival output
When the starting time of the inverter exceeds the time set
by PC-29, the ON signal will be output.
Y2 (Normal terminal) output delay time
Relay 1 output delay time
Relay 2 output delay time
It is used to set the delay time when the state of Y terminal changes.
Y terminal effective state selection
Ones bit: Y1
Tens bit: Y2
Hundreds bit: reserved
Thousands bit: relay 1
Ten thousand bit: relay 2
0: Positive logic close valid / open invalid
1: Negative logic close invalid/open valid
Y2 (high speed pulse) output function
selection
0~13 parameters and functions are shown