111
Setting
value
Function
Explanation
32
Lower frequency arrival
(operation related)
When the operating frequency reaches the lower frequency,
the ON signal is output. The signal is off in the shutdown
state.
33
Fault output (free shutdown fault
and no output when under
voltage)
Fault of free shutdown and no output when under voltage.
34
Module temperature arrival
When the inverter module radiator temperature (P8-19)
reaches the set module temperature (PC-47), the ON signal
is output
35
Fault output (output only after
fault shutdown)
When the frequency converter fails, and the fault
processing mode is continue to run, the frequency converter
alarm output.
36
Motor over temperature alarm
Motor temperature acquisition value is greater than P7-37
value, alarm output
37
Speed direction
When the inverter is in reverse operation, it outputs ON
signal.
38
Load dropping
Load suddenly unloaded
39
Software overcurrent output
Refer to PC-40, PC-41.
40
Current detection arrival output
Refer to PC-38, PC-39.
41
Current run time arrival
When the starting time of the inverter exceeds the time set
by PC-29, the ON signal will be output.
42
Bus voltage reached
Refer to PC-65, PC-66
Parameter
Name
Range
P3-06
Y1 output delay time
0.0~3600.0s
P3-07
Y2 (Normal terminal) output delay time
0.0~3600.0s
P3-09
Relay 1 output delay time
0.0~3600.0s
P3-10
Relay 2 output delay time
0.0~3600.0s
It is used to set the delay time when the state of Y terminal changes.
Parameter
Name
Range
P3-11
Y terminal effective state selection
Ones bit: Y1
Tens bit: Y2
Hundreds bit: reserved
Thousands bit: relay 1
Ten thousand bit: relay 2
0: Positive logic close valid / open invalid
1: Negative logic close invalid/open valid
Parameter
Name
Range
P3-12
Y2 (high speed pulse) output function
selection
0~13 parameters and functions are shown

Table of Contents