Input phase lack protection
Ones bit: input phase lack protection
Tens bit: Contactor closing protection
selection
0: Forbidden
1: Allowed
Select whether to protect the input phase loss or contactor closing.
Output phase lack protection
Choose whether to protect the output phase lack. If 0 is selected, the fault will not be reported when the actual
output phase lack occurs. At this time, the actual current is larger than the current displayed on the panel. There
is a risk. Please use it cautiously.
Power on short circuit to ground
protection function
When the frequency converter is powered on, it can detect whether the motor is short circuited to the ground.
If this function is effective, the UVW end of the inverter will have voltage output for a period of time after
power on.
Action selection of fault relay during
automatic fault reset
If the frequency converter is equipped with automatic fault reset function, fault Y action during automatic fault
reset can be set through P7-42 (P7-42 is only effective for Y terminal).
Interval time of automatic fault reset
This parameter is used as the wait time from the fault occurrence to the automatic reset of the fault.
Fault automatic reset times
This parameter is used as the times of automatic reset after the failure of the frequency converter, and the
frequency converter maintains the failure state after exceeding the set value.
Protection action 1 when fault
Ones bit: motor overload (Err 10)
0: free stop
1: stop as stop mode
Tens bit: input phase lacking (Err11)
0: free stop
1: stop as stop mode
Hundreds bit: output phase lacking (Err12)
0: free stop