Display the accumulated running time of frequency converter. When the running time reaches the set running
time PC-32, the multi-function digital output function of frequency converter outputs ON signal.
Display the cumulative power on time of frequency converter since leaving factory.
When this time reaches the set power on time (PC-30), the multi-function digital output function of frequency
converter outputs ON signal.
Cumulative power consumption
Display the cumulative power consumption of the inverter so far.
Inverter module radiator temperature
Displays the temperature of IGBT inverter module.
When the output power (U0-06) does not correspond to the expected value, the output power can be linearly
corrected by this value.
Load speed display factor
Load speed display decimal position
One digits: number of decimal points of U0-16
0: 0 decimal places
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
Ten digits: number of U0-17 decimal points
1: 1 decimal place
2: 2 decimal places
When the load speed needs to be displayed, the corresponding relationship between the output frequency of the
inverter and the load speed can be adjusted through this parameter.
If the load speed display coefficient P8-21 is 2.0000 and the decimal points of load speed P8-22 are 2 (2
decimal points), when the inverter operates at 40.00Hz, the load speed: 40.00*2.0000=80.00 (2 decimal places
display).
If the inverter is in the shutdown state, the load speed is displayed as the speed corresponding to the set
frequency, that is, "set load speed". For example, if the frequency is set to 50.00Hz, the load speed in shutdown