145
VH6 provided four groups of acceleration and deceleration time, which are P0-18/P0-19 and above parameters.
PC-09 is used to set the unit of acceleration and deceleration time for four groups.
The base frequency of acc/dec time
0: max output frequency P0-13
1: setting frequency
2: 50Hz
The acceleration and deceleration time is the time accelerating from 0 to the frequency set by PC-10. If PC-10 is
1, the acceleration of the motor changes.
Switching frequency point between
acceleration time 1 and acceleration
time 2
0.00Hz~max output frequency
Switching frequency point between
deceleration time 1 and deceleration
time 2
0.00Hz~ max output frequency
When controlling motor 1, you can choose different acceleration and deceleration time.
Note: when using this function, the multi-function terminal function cannot select the acceleration and
deceleration time switching.
0.00Hz~max output frequency
0.00Hz~max output frequency
0.00Hz~max output frequency
When the set frequency is within the range of jumping frequency, the actual running frequency will run at the
jumping frequency close to the set frequency. By setting the jumping frequency, the inverter can avoid the
mechanical resonance point of the load.
VH6 can set two jump frequency points. If both jump frequencies are set to 0, the jump frequency function will
be cancelled.
Please refer to the figure below for the principle of jump frequency and jump frequency amplitude.