When PC-26 = 1, the timing function is turned on, the current running time U0-31 is greater than the value set
by PC-28, the inverter stops running, and Y outputs ON signal by assigning function code 26 to Y terminal.
The value of current time U0-31 is greater than the value set by PC-29. By assigning function code 41 to Y
terminal, Y outputs ON signal, but the inverter will not stop running.
When the accumulated operation time of P8-10 is greater than the set operation arrival time of PC-32, the
frequency converter will stop operation. By assigning function code 29 to the Y terminal, the Y terminal will
output ON signal.
When the cumulative power on time of P8-11 is greater than the power on arrival time set by PC-30, the
inverter will stop running. By assigning function code 25 to the Y terminal, the Y terminal will output ON
signal.
Current reached detection value 1
0.0%~300.0% (motor rated current)
Current reached detection 1 range
0.0%~300.0% (motor rated current)
Current reached detection value 2
0.0%~300.0% (motor rated current)
Current reached detection 2 range
0.0%~300.0% (motor rated current)
When the output current of the frequency converter is within the set positive and negative detection width of
current arrival, the multi-function Y outputs ON signal.
VH6 provides two groups of arrival current and detection width parameters. The following figure is the function
diagram.
Timing function selection
Present operation reached time
Setting power on reached time
Setting operation reached time