149
Parameter
Name
Range
PC-38
Zero current detection value
0.0%~300.0% (motor rated current)
PC-39
Zero current detection delay time
0.01s~600.00s
When the output current of the inverter is less than or equal to the zero current detection level and the duration
exceeds the zero current detection delay time, the Y terminal of the inverter outputs ON signal.
Parameter
Name
Range
PC-40
Software overcurrent point
00.0% (not detect)
10.1%~300.0% (motor rated current)
PC-41
Software overcurrent detection delay
time
0.00s~600.00s
When the output current of the frequency converter is greater than or exceeds the limit detection point, and the
duration exceeds the software over-current point detection delay time, the Y terminal of the frequency converter
outputs ON signal.
Parameter
Name
Range
PC-42
AI1 input voltage lower limit
0.00V~PC-43
PC-43
AI1 input voltage upper limit
PC-42~10.50V
When the value of analog input AI1 is greater than PC-43, or AI1 input is less than PC-42, Y terminal of
frequency converter outputs "AI1 input overrun" ON signal, which is used to indicate whether the input voltage
of AI1 is within the set range.
Parameter
Name
Range
PC-44
Over voltage point
540~810V (380V models)
200~400V (220V models)
It is used to set the voltage value of inverter overvoltage fault. The factory value of 380V voltage level inverter
overvoltage point is 810V, and the factory value of 220V voltage level inverter overvoltage point is 400V.
Parameter
Name
Range
PC-45
Under voltage point
200~537V (380V models)
200~400V (220V models)
It is used to set the voltage value of the inverter under voltage fault Err08. The factory value of the 380 V
voltage level inverter is 350 V, and the factory value of the 220 V voltage level inverter is 200 V.
Parameter
Name
Range
PC-46
Operation action when the frequency
is lower than lower limit frequency
0: Run at lower limit frequency
1: Stop
2: Run at zero speed
Parameter
Name
Range
PC-47
Module temperature reached
0~100
When the inverter radiator temperature reaches the temperature, the inverter Y terminal outputs the "module
temperature reaches" ON signal.
Parameter
Name
Range
PC-48
Fan control
0: The fan runs during operation
1: The fan is running all the time