170
Parameter
Name
Min unit
U0-09
AI1 voltage (V)/current (mA)
0.01V/0.01mA
U0-10
AI2 voltage (V)/current (mA)
0.01V/0.01mA
U0-11
AI3 voltage (V)/current (mA)
0.01V/0.01mA
Whether the analog input is voltage or current, U0-09 ~ U0-11 are displayed as the voltage value, and the
current value needs to be multiplied by 2 on the basis of U0-09~U0-11.
For example: AI1 input 5V analog voltage, U0-09 display value should be 5V, AI input 10mA analog current,
then U0-09 display value is 5.
Parameter
Name
Min unit
U0-12
PULSE input frequency
1Hz
U0-13
PULSE input frequency (Hz)
0.01kHz
Parameter
Name
Min unit
U0-14
PID setting
1
U0-15
PID feedback
1
PID setting = PID setting (percentage) *PA-20
PID feedback = PID feedback (percentage) *PA-20
Parameter
Name
Min unit
U0-16
Load speed display
1
The set load speed is displayed during shutdown and the running load speed is displayed during operation. The
value displayed by the parameter can be adjusted according to P8-21 and P8-22. See Group P8 parameter
description for details.
Parameter
Name
Min unit
U0-17
Feedback speed (Hz)
Depend on P8-22
Display the given frequency.