174
Parameter
Name
Min unit
1: Faulty
Bit3:Frequency
reaches the set
frequency
(supported by 3720
and above
versions)
Bit8~Bit15:Alarm
code(supported by
3720 and above
versions)
For example: U0-69=H.2C04, hexadecimal 2C converted to decimal is 44, which means that the current fault
code is Err44, hexadecimal 04 converted to binary is 100, which means that it is in a fault state.
Parameter
Name
Min unit
U0-70
Communication feedback motor speed /0.01Hz
0.01Hz
Display the motor speed fed back by communication, unit:0.01 Hz.
Parameter
Name
Min unit
U0-71
Communication feedback motor speed /RPM
1RPM
Display the motor speed fed back by communication, unit: rpm.
Parameter
Name
Min unit
U0-72
Special current display for communication card
-
U0-73
Communication card error status
-
U0-74
Motor actual output torque
0.01%
The output torque is based on the rated current of the inverter, and the maximum value corresponds to P6-11
and PF-02.