Group P2: Input terminal function parameters
Parameter
Name
Setting range
Default
value
Modify
Modbus
address
3: three wire mode 2
P2-11
XI terminal UP/DOWN changing
rate
0.001Hz/s~50Hz/s
1.00Hz
/s
020BH
P2-12
XI terminal filtering time
0.000s~1.000s
0.010s
020CH
P2-13
X1 delay time
0.0s~3600.0s
0.0s
×
020DH
P2-14
X2 delay time
0.0s~3600.0s
0.0s
×
020EH
P2-15
X3 delay time
0.0s~3600.0s
0.0s
×
020FH
P2-16
XI terminal effective state
selection 1
0: High level valid
1: Low level valid
Ones bit: X1
Tens bit: X2
Hundreds bit: X3
Thousands bit: X4
Ten thousands bit: X5
00000
×
0210H
P2-17
XI terminal effective state
selection 2
0: High level valid
1: Low level valid
Ones bit: X6
Tens bit: X7
00000
×
0211H
P2-18
AI curve 1 min setting
0.00V~P2-20
0.00V
0212H
P2-19
AI curve 1 min setting
corresponding frequency
percentage
-100.0%~+100.0%
0.0%
0213H
P2-20
AI curve 1 max setting
P2-18+10.00V
10.00V
0214H
P2-21
AI curve 1 max setting
corresponding frequency
percentage
-100.0%~+100.0%
100.0%
0215H
P2-22
AI curve 2 min setting
0.00V~P2-24
0.00V
0216H
P2-23
AI curve 2 min setting
corresponding frequency
percentage
-100.0%~+100.0%
0.0%
0217H
P2-24
AI curve 2 max setting
P2-22~+10.00V
10.00V
0218H
P2-25
AI curve 2 max setting
corresponding frequency
percentage
-100.0%~+100.0%
100.0%
0219H
P2-26
AI curve 3 min setting
0.00V~P2-28
0V
021AH
P2-27
AI curve 3 min setting
corresponding frequency
percentage
-100.0%~+100.0%
0.0%
021BH
P2-28
AI curve 3 max setting
P2-26~+10.00V
10.00V
021CH
P2-29
AI curve 3 max setting
corresponding frequency
percentage
-100.0%~+100.0%
100.0%
021DH
P2-30
AI curve 4 min setting
0.00V~P2-32
0.00V
021EH