56
Group P2: Input terminal function parameters
Parameter
Name
Setting range
Default
value
Modify
Modbus
address
P2-31
AI curve 4 min setting
corresponding frequency
percentage
-100.0%~+100.0%
0.0%
021FH
P2-32
AI curve 4 inflection point 1
setting
P2-30~P2-34
10.00V
0220H
P2-33
AI curve 4 inflection point 1
setting corresponding frequency
percentage
-100.0%~+100.0%
100.0%
0221H
P2-34
AI curve 4 inflection point 2
setting
P2-32V~P2-36
0.00V
0222H
P2-35
AI curve 4 inflection point 2
setting corresponding frequency
percentage
-100.0%~+100.0%
0.0%
0223H
P2-36
AI curve 4 max setting
P2-34~+10.00V
10.00V
0224H
P2-37
AI curve 4 max setting
corresponding frequency
percentage
-100.0%~+100.0%
100.0%
0225H
P2-38
AI curve 5 min setting
-10.00V~P2-40
0V
0226H
P2-39
AI curve 5 min setting
corresponding frequency
percentage
-100.0%~+100.0%
0.0%
0227H
P2-40
AI curve 5 inflection point 1
setting
P2-38~P2-42
10.00V
0228H
P2-41
AI curve 5 inflection point 1
setting corresponding frequency
percentage
-100.0%~+100.0%
100.0%
0229H
P2-42
AI curve 5 inflection point 2
setting
P2-40~P2-44
0.00V
022AH
P2-43
AI curve 5 inflection point 2
setting corresponding frequency
percentage
-100.0%~+100.0%
0.0%
022BH
P2-44
AI curve 5 max setting
P2-42~+10.00V
10.00V
022CH
P2-45
AI curve 5 max setting
corresponding frequency
percentage
-100.0%~+100.0%
100.0%
022DH
P2-54
AI curve selection
Ones bit: AI1 curve selection
1: Curve 1 (2 points, see P2-18 ~ P2-21)
2: Curve 2 (2 points, see P2-22 ~ P2-25)
3: Curve 3 (2 points, see P2-26 ~ P2-29)
4: Curve 4 (4 points, see P2-30 ~ P2-37)
5: Curve 5 (4 points, see P2-38 ~ P2-45)
Tens bit: AI2 curve selection, ditto
Hundreds bit: AI3 curve selection, ditto
321
0236H

Table of Contents