8 expansion devices
Items Analogue Input (AD)
Temp. inputPT
Analogue output (DA)
Current
0
20mA
4
20mA
Analogue Input
Voltage
05V
010V
PT100 -
Temperature Range - -100~350 -
Max input range DC040mA - -
Current
010V
05V
Analogue output
range
- -
Voltage
020mA
420mA
Digital input range - - 10 bits binary (0~1023)
Digital Output range
16 bits binary (0~65535) -1000~3500 -
Distinguish Ratio
1/16383(16Bit) 0.01 1/1023(10Bit)
PID Output value
0~K4095 -
Integral precision
0.8% ±0.01 0.8%
Convert speed 20ms/CH 3ms/CH
Power supply DC24V±10%100mA
Specification 2
2CH 16bits analogue input2CH PT100 temperature input and 2CH 10bits analogue output
2CH input/output is current, voltage selectable (current: 0~20mA4~20mA; voltage: 0~5V
0~10V), select via XCPPro;
2CH A/D and 2CH PT input has PID auto tune function;
Adopt DC-DC power supply isolation design, enhance the anti-interfere ability;
The display precision is 0.01
Set each channel’s PID value separately, equipped separate register space;
Support real time PID auto tune function; enable the device to PID auto tune under every
status (cold status, heating status, transition status etc), get the best PID values;
Realize data exchange with FROM and TO instructions, enhance the flexibility, reduce the
data exchange quantity, expand the data memory space;