17
2. Main body specification parameters
2-1Specification parameters
2-1-1General specification
This specification parameter table is also applicable to XSDH, XSLH and XS3 series PLC.
Item
Specification
Anti-noise
Noise voltage 1000Vp-p 1us pulse 1 minute
Air
No corrosive and combustible gas
Ambient temperature
0~60
Ambient humidity
5%~95% (no condensation)
Communication port 1
RS232 (COM1), connect upper computer, HMI for programming or debugging
Communication port 2
RS485 (COM2), connect intelligent instrument, frequency converter, etc
Communication port 3
RJ45 (LAN1), support Ethernet communication, realize remote control of industrial field
equipment
Communication port 4
RJ45 (LAN2), support EtherCAT bus control
Communication port5
CAN, support CANopen bus control (only for XSLH)
Installation
Fix with M3~M4 screws
Grounding (FG)
The third grounding (It shall not be grounded in common with strong current system)
Note: Separate grounding or common grounding shall be adopted for grounding, and public grounding shall not be
adopted.
2-1-2Performance specification
Item
XSDH-60A32-E
XS3-26T4
XSLH-30A32
Programming
method
ST, SFC, FBD, CFC, LD, IL
Main processor
Dominant frequency 1GHz
Dominant frequency 800MHz
Dominant frequency 1GHz
User program
capacity
1
32MB
Data capacity
32MB
Power-off
holding capacity
6MB
I/O
points
Total
60 points
26 points
30 points
Input
36 points X0~X43
18 points X0~X21
14 points X0~X15
XS
PLC
Other devices
Other devices
Other devices
XS
PLC
XS
PLC
Separate grounding
Common grounding
Public grounding