41
6. Output specification and wiring method
6-1. Output specification
(1) Normal transistor output
External power supply
Below DC5~30V
Circuit insulation
Optocoupler insulation
Action indicator
LED light
Max load
Resistive
load
0.3A
inductive
load
7.2W/DC24V
Light load
1.5W/DC24V
Min load
DC5V 2mA
Open circuit leakage
current
< 0.1mA
Response
time
OFF→ON
< 0.2ms
ONOFF
< 0.2ms
Note:
The PLC is generally equipped with a plug-in spring connector to facilitate wiring when it leaves the factory.
The connector requires that the stripped length of the wire shall be at least 1.5cm. When wiring, press the
yellow spring switch with a small screw drive, insert the wire into the corresponding socket, and release the
spring switch.
6-2. Transistor output
(1) General transistor output
External Power Supply
Please use DC5~30V power supply to drive the load.
Circuit Isolation
Inside PLC, we use photoelectric couplers to isolate between internal circuits and output transistors
Action Display
When photoelectric couplers drive, LED will be ON and the output transistors will be ON.
Response Time
The time interval that PLC from photoelectric couplers energizing (or cutting) to transistor ON (or OFF) is
below 0.2ms.
Output current
The current it outputs is 0.3A per point. But limited by the temperature rising, every 4 points current add
up to 0.5A.
Open circuit current
Below 0.1mA.