HOOD SERVICE PROCEDURES
Complete VFD manual available at www.xltovens.com.
Allen Bradley Power Flex 4M Restoring XLT Hood Defaults
To reset VFD settings change P112 to one (1) . The VFD will reset to factory default settings. To
cycle power, turn circuit breaker off and on and the HMC will load the factory parameters into the
VFD.
P105=65 Maximum Frequency
P106=2 Start Source
P108=4 Speed Reference
P110=2 Decel Time
A451=9 Auto Reset Tries
A452=60 Auto Reset Delay
T201=2 Terminal Block Group (I/O) Terminal 5
T202=6 Terminal Block Group (I/O) Terminal 6
A404=60 Jog Frequency
Test run the motor by turning on one of the oven/hood buttons located on the HUI.