7.4 Connect a 4–20 mA level sensor
Select one of the following steps to connect the two wires from the level
sensor to the terminals.
Condition Action
The sensor is passive. Voltage is supplied by the control unit. Connect to the + and IN terminals.
The sensor is active. Voltage is supplied by the sensor. Connect to the IN and terminals.
7.5 Connect a pump sensor circuit
1. Pump 1
2. Pump 2
Connect the pump sensor circuits to terminals T1 and T2.
7 Electrical Installation
Flygt FGC 400 Installation, Operation, and Maintenance 21