Number Part Description
11 Terminals See Terminals.
8.2 Commissioning
For more information about the menus, see User Interface (page 39).
Power on the controller.
Condition Action
First start of the controller without USB
drive.
1. Select Setup Wizard.
2.
Proceed with Run the setup wizard (page
29).
First start of the controller with USB drive. Select Restore from USB and follow the instructions.
Start of controller with existing
configuration
The Home menu appears.
The setup wizard is always accessible.
8.3 Run the setup wizard
1. Start through the wizard.
Use the jog wheel to select and confirm.
Menu Action
Language Select the language.
Unit of Measurement Select metric or imperial system. This option appears only when the English
language has been selected.
Date/Time Settings Navigate, select, and change to the correct date and time. Confirm the
settings.
Number of Pumps Select number of pumps.
2. Select and configure the level sensor.
Option Action
Analog Select and configure:
1. Sensor Range
2. Duty Start Level
3. Standby Start Level
4. Pump Stop Level
Open Bell Select and configure:
1. Duty Start Level
2. Standby Start Level
Float Switches Go to the next menu.
3. Continue through the wizard.
8 System Setup and Operation
Flygt FGC 400 Installation, Operation, and Maintenance 29