The start and stop levels are changed from the Well menu or from the Settings
menu.
Change the start and stop levels from the Well menu.
1. On the Home menu, select the well symbol.
2. Select one of the parameters.
Duty Start Level
Standby Start Level
Pump Stop Level
Low Level Activation Level
Low Level Deactivation Level
High Level Activation Level
High Level Deactivation Level
3. Select, change, and confirm the new start or stop level.
Change the start and stop levels in the Settings menu.
4. Go to Settings > Pump Control.
5. Select, change, and confirm the new start or stop level.
8.4.2 Configure the general-purpose digital input
1. Go to Settings > Pump Control > GP Input Usage.
2. Select the device that is connected to the general-purpose digital input.
3. Go to Settings > Alarms.
4. Configure the alarm for the device that is connected to the general-purpose
digital input.
Device GP input setting Alarm Setting
Low level float switch Low Level Float Float Low Level Activation Delay
Deactivation Delay
Control Lamp
Control Relay
Overflow float switch Station Overflow Station Overflow
Alarm switch Personnel Alarm Personnel Alarm Warning Interval
Alarm Interval
General Settings
Control Lamp
Control Relay
8.4.3 Change the profile
1. On the Home menu, select the Well symbol.
2. Select Active Profile.
3. Select and confirm the new profile.
8.4.4 Set the date and time
1. Go to Settings > Global Settings > Date/Time Settings.
2. Open Change Date/Time.
8 System Setup and Operation
Flygt FGC 400 Installation, Operation, and Maintenance 31