21
Chapter 5. COMMUNICATION DATA TABLE
■ Operating status related data
Note
• For RD and WD commands, the data is required four hexadecimal digits.
• The flow rate unit "L/min" becomes "mL/min" in MQV9200.
Item Data range RAM EEPROM Remarks
Address R W Address R W
Decimal Decimal
(Hexadecimal) (Hexadecimal)
Alarm status bit Refer to *1 1201 ❍ ✕ 4201 ✕✕For RS command,
(04B1) (1069) status is shown in
decimal numbers
Event status bit Refer to *2 1202
❍ ✕ 4202 ✕✕ For RS command,
(04B2) (106A) status is shown in
decimal numbers
Control status bit Refer to *3 1203
❍ ✕ 4203 ✕✕ For RS command,
(04B3) (106B) status is shown in
decimal numbers
Operation mode 0: Valve full close 1204
❍❍ 4204 ❍❍ When the valve is in full
1:Valve control (04B4) (106C) close or full open by
2:Valve full open external inputs, write
operation is disabled.
Instantaneous SP
0:SP-0 1205 ❍❍ 4205 ❍❍When SP No. switching
No. in use 1:SP-1 (04B5) (106D) is selected by external
2:SP-2 inputs, write operation
3:SP-3 is disabled.
4:SP-4 The value larger than
5:SP-5 the one selected with
6:SP-6 SP No.(Address 5004)
7:SP-7 of the function setup
can not be written.
Instantaneous (0 to 100%FS) 1206
❍ ✕ 4206 ✕✕
SP value in use L/min (04B6) (106E)
Instantaneous (0 to 100%FS) 1207
❍ ✕ 4207 ✕✕
PV value L/min (04B7) (106F)
Valve actuation 0.0 to 100.0% 1208 ❍ ✕ 4208 ✕✕ The decimal point is
current (04B8) (1070) removed .
The value in the data
range (L/min) is the
value removed
decimal point that
obtained by full scale
flow rate multiplied by
the percentage in
parentheses.