22
Chapter 5. COMMUNICATION DATA TABLE
*1 : Alarm status bit configuration (Address 1201) 0: Normal 1: Error
*2 : Event status bit configuration (Address 1202) 0: OFF 1: ON
*3 : Alarm status bit configuration (Address 1203) 0: OFF 1: ON
Bit No. Description
0 Event output 1 status
1 Event output 2 status
2 Undefined (0 fixed)
3 External contact 1 input status
4 External contact 2 input status
5 External contact 3 input status
6 External 3-stage switching input status 1 (0V input)
7 External 3-stage switching input status 2 (5V input)
Bit No. Description
0 OK lamp (PV control status)
0: Light-out 1: Lighting (Instantaneous PV OK)
1 Slow start operation
0: Normal operation 1: Slow start operation
2 Digital setting / Analog setting
0: Digital setting 1: Analog setting
3 Totalizing count status
0: Totalized flow PV < Totalized flow event SP
1: Totalized flow PV
≥
Totalized flow event SP
4 SP ramp control function
0: Function disabled 1: SP ramp control enabled
5 Undefined (0 fixed)
6 Undefined (0 fixed)
7 Undefined (0 fixed)
Bit No. Description
0 Deviation lower limit alarm of instantaneous flow rate (AL01)
1 Deviation upper limit alarm of instantaneous flow rate (AL02)
2 Valve amperage lower limit alarm (AL11)
3 Valve amperage upper limit alarm (AL12)
4 Sensor error (common to AL81, AL82 and AL83)
5 Input / output adjustment data error (AL91)
6 Sensor calibration data error (AL92)
7 User setup data error (AL93)
8 Valve overheat prevention limit operation (AL71)
9 Sensor error 1 (AL81)
10 Sensor error 2 (AL82)
11 Sensor error 3 (AL83)