25
Chapter 5. COMMUNICATION DATA TABLE
Item Data range
RAM EEPROM
Remarks
Address
RW
Address
RW
Decimal Decimal
(Hexadecimal) (Hexadecimal
Input range selection (2)Analog output selection 2005 ❍❍ 5005 ❍❍
of analog setup is set at current output (07D5) (138D)
(analog SP input (C-06 = 2, 3, 6, or 7)
range selection) 0 : 0 to 20mA external
reference input
1 : 0 to 20mA external
reference input
2 : 4 to 20mA external
reference input
Analog output type 0: 0 to 5V instantaneous 2006
❍❍ 5006 ❍❍
and range selection flow rate output (07D6) (138E)
(analog PV output 1: 1 to 5V instantaneous
range selection) flow rate output
2: 0 to 20mA instantaneous
flow rate output
3: 4 to 20mA instantaneous
flow rate output
4: 0 to 5V setting flow rate
output
5: 1 to 5V setting flow rate
output
6: 0 to 20mA setting flow
rate output
7: 4 to 20mA setting flow
rate output
Event 1 output type 0:
Not used (OFF fixed)
2007 ❍❍ 5007 ❍❍
assignment
1: ON when the totalized
(07D7) (138F)
Event 2 output type flow event occurs 2008
❍❍ 5008 ❍❍
assignment 2: Totalized pulse output (07D8) (1390)
3: ON
when the flow rate is OK
4: ON in control mode
5: ON in fully open mode
6: ON in control or fully
open mode
7: ON in fully closed mode
8: PV upper limit event
9: PV lower limit event 1
10
:PV lower limit event 2
-1 to -10: Inverse output of
above 1 to 10
(Normal operation: ON,
Event occurrence: OFF)
External 3-stage 0: Not used 2009
❍❍ 5009 ❍❍
switching function 1: Switching of operating (07D9) (1391)
assignment mode 1
2: Switching SP No.
3: Switching of totalizing
operation
4: Switching of analog I/O
voltage range
(simultaneous external
switching of C-05 and
C-06)
5: Switching of operating
mode 2