Chapter 5. COMMUNICATION DATA TABLE
Item Data range
RAM EEPROM
Remarks
Address
RW
Address
RW
Decimal Decimal
(Hexadecimal) (Hexadecimal)
External contact 0: Not used 2010 ❍❍ 5010 ❍❍
input 1 function
1:
Reset totalized flow count
(07DA) (1392)
assignment
2: Stop totalizing flow
External contact
count
2011
❍❍ 5011 ❍❍
input 2 function
3:
Switching of
SP No.
(07DB) (1393)
assignment 4:
Switching of instantaneous
External contact
flow rate setup method
2012 ❍❍ 5012 ❍❍
input 3 function
5:
Valve forced fully closed
(07DC) (1394)
assignment
6: Valve forced fully open
7: Switching of slow start
operation or switching of
instantaneous SP ramp
control operation
8: Switching of operating
mode
(control by contact ON,
forced fully closed by
contact OFF)
9: Flow rate zero adjust-
ment
10
:Switching of gas type
setup
11
:
Switching of flow rate range
12
:Switching of SP ramp
13
:Alarm reset
Automatic valve 0: Function disabled 2013
❍❍ 5013 ❍❍
shut-off when the 1: Function enabled (07DD) (1395)
totalized flow
event occurs
On/off of totalized 0: Function disabled 2014
❍❍ 5014 ❍❍
flow reset function 1: Function enabled (07DE) (1396)
at start of control
Flow rate alarm 0: Function disabled 2015
❍❍ 5015 ❍❍
setup type 1: Only upper limit alarm (07DF) (1397)
2: Only lower limit alarm
3: Upper/lower limit alarm
Operation selection 0: Control continued 2016
❍❍ 5016 ❍❍
at alarm occurrence (alarm ignored) (07E0) (1398)
1: Forced fully closed
2: Forced fully open
Slow start setup 0: Slow start disabled 2017
❍❍ 5017 ❍❍
1 to 8: Slow start enabled (07E1) (1399)
(equivalent to approx. 1
to 6 seconds settling
time)