Parameter setup related data
Note
For RD and WD commands, the data is required four hexadecimal digits.
When the function setup is not valid, parameter setup is invalid.
The decimal point of all data is removed.
Chapter 5. COMMUNICATION DATA TABLE
Item Data range
RAM EEPROM
Remarks
Address
RW
Address
RW
Decimal Decimal
(Hexadecimal) (Hexadecimal)
Instantaneous flow rate (0.5 to 100%FS) 2201 ❍❍ 5201 ❍❍
O.K judgment range (0899) (1451)
Instantaneous flow rate (0.5 to 100%FS) 2202
❍❍ 5202 ❍❍
O.K judgment hysteresis (089A) (1452)
Instantaneous flow rate (0.5 to 100%FS) 2203
❍❍ 5203 ❍❍
deviation upper limit alarm (089B) (1453)
Instantaneous flow rate (0.5 to 100%FS) 2204
❍❍ 5204 ❍❍
deviation upper limit alarm (089C) (1454)
hysteresis
Instantaneous flow rate (0.5 to 100%FS) 2205
❍❍ 5205 ❍❍
deviation lower limit alarm (089D) (1455)
Instantaneous flow rate (0.5 to 100%FS) 2206
❍❍ 5206 ❍❍
deviation lower limit alarm (089E) (1456)
hysteresis
Instantaneous flow rate 0.5 to 999.9s 2207
❍❍ 5207 ❍❍
deviation alarm judgment (089F) (1457)
delay time
Event output 1 delay 0.0 to 999.9s 2208
❍❍ 5208 ❍❍
(08A0) (1458)
Event output 2 delay 0.0 to 999.9s 2209
❍❍ 5209 ❍❍
(08A1) (1459)
User setup conversion 0.04 to 9.999 2210
❍❍ 5210 ❍❍
factor (08A2) (145A)
Valve amperage upper 0.1 to 100.0% 2211
❍❍ 5211 ❍❍
limit alarm (08A3) (145B)
Valve amperage lower 0.0 to 99.9% 2212
❍❍ 5212 ❍❍
limit alarm (08A4) (145C)
Event output 1 upper/ (0 to 100%FS) 2213
❍❍ 5213 ❍❍
lower limit flow rate setup (08A5) (145D)
Event output 2 upper/ (0 to 100%FS) 2214
❍❍ 5214 ❍❍
lower limit flow rate setup (08A6) (145E)
SP ramp control ramp 1 MQV9200/9500: 2215
❍❍ 5215 ❍❍
0.0 to 999.9 (08A7) (145F)
SP ramp control ramp 2 MQV0002/0005: 2216
❍❍ 5216 ❍❍
0.000 to 9.999 (08A8) (1460)
MQV0010/0020/
0050:
0.00 to 99.99
MQV0200/0500:
0.0 to 999.9
MQV1000:
0 to 9999
Delay does
not apply to
totalizer pulse
output.
30
Unit: L/min
(standard)
(mL/min
(standard) for
the MQV9200.)
Unit: L/min
(standard)
(mL/min
(standard) for
the MQV9200.)