4 Connection
DX100 4.3 Connection Methods
4-9
II) Perform grounding in accordance with all relevant local and
national electrical codes. The size of ground wire must the
same as listed on table 4-2 “DX100 Power Capacity, Cable
Sizes, and Breaker Capacities” at page 4-5.
Fig. 4-12: Exclusive Grounding
(3) Connect the primary power supply cable.
Fig. 4-13: Connection of the Primary Power Supply Cable
NOTE
The customer must prepare the ground wire.
NOTE
Don’t connect the grounding wire with the wires for the elec-
tric power source, the welder, etc.
Ground in accordance with all relevant governmental regu-
lations when using metallic ducts, metallic conduits, and
cable tray to construct the cable.
Exclusive Grounding
100 ohm maximum
ground resistance