8Alarm
DX100 8.3 Alarm Message List
8-579
4964 CONST.SPD
MEASURE MULTI
REQ (SV)
Software operation
error occurred
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
4965 DIN SIGNAL
SPECIFIC. ERROR
(SV)
Sub Code: Signifies the axis in
which the alarm occurred
Setting error Check the settings for jobs.
4966 DB REGIST NOT
INSTALLED(SV)
Connection failure (1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, check the connection and inserting state of the
following cables and connectors.
·DB resist of CN585 amplifier
·Short-circuit connector CN585 amplifier
DB resist board
failure
The DB resist may be fired. Replace the DB resist.
Module
failure(SERVOPACK
)
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the SERVOPACK.
4967 RATED
CURRENTAND
MAXIMUM
CURRENT HIGH
RESOLUTION
PRM
UNDEFINED(SER
VO)
Setting error Check the settings for condition files.
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy