Alarm List
Alarm Number (1000 to 1999)
Alarm List-346
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
6 CRC error YSF25 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF25 board. Save the
CMOS.BIN before replace the board to be safe.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
CRC error other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
7 YSF25 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF25 board. Save the
CMOS.BIN before replace the board to be safe.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1613 F-SAFE
ENCODER COMM.
ERR 1
Sub Code: Signifies the axis
in which the alarm occurred
Blown fuse If AL1962 "EAXA21 board failure" occurred simultaneously with this
alarm,
Replace the fuse(F1) in the EAXA21 board.
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy