EasyManua.ls Logo

YASKAWA GA500 series - Page 268

YASKAWA GA500 series
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.7 F: Options
268 YASKAWA TOEPYAIGA5002A GA500 Programming
F6-16
[Gateway Mode]
H5-01
[Drive Node
Address]
*1
H5-02
[Communication
Speed Selection]
H5-03
[Communication
Parity Selection]
H5-06
[Drive Transmit
Wait Time]
H5-09
[CE Detection
Time]
b1-01
[Frequency
Reference
Selection 1]
b1-02
[Run Command
Selection 1]
Drive 2
(Slave Drive)
0 02
*3 *4 *5
5 ms (Default)
*6
0.9 s
*7
2 [Memobus/Modbus
Communications]
*8
2 [Memobus/Modbus
Communications]
*8
Drive 3
(Slave Drive)
0 03
*3 *4 *5
5 ms (Default)
*6
0.9 s
*7
2 [Memobus/Modbus
Communications]
*8
2 [Memobus/Modbus
Communications]
*8
Drive 4
(Slave Drive)
0 04
*3 *4 *5
5 ms (Default)
*6
0.9 s
*7
2 [Memobus/Modbus
Communications]
*8
2 [Memobus/Modbus
Communications]
*8
*1 Re-energize the drive to apply the new settings.
*2 Specify the number of slave drives you will connect.
*3 Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
*4 Set a slave address that is different from other slave devices.
*5 Enter the same value that you use for the master drive.
*6 To correctly detect the response timeout, do not change the value of H5-06 from the default value.
*7 Set H5-09 0.9. When H5-09 < 0.9, the drive will detect CE [Modbus Communication Error] before it detects a response timeout.
*8 On each slave drive, set b1-01 [Frequency Reference Selection 1] and b1-02 [Run Command Selection 1] to 2 [Memobus/Modbus
Communications].
An Overview of Gateway Mode
When in gateway mode, the drive will operate as shown in Table 2.45.
A - Controller
B - Communication Option
C - Master Drive (Drive 0)
D - Slave Drives (Drives 1 to 4)
Table 2.45 Operation in Gateway Mode
Controller to Communication Option Communication Option to Master Drive (Drive 0)
Master Drive (Drive 0) to Slave Drives (Drives 1 to
4)
The controller and card communicate in the format of
each field bus communications protocol.
Drive 0 sends commands and monitors through normal
field bus communications.
The special registers of Drive 0 use read and write to
send commands to and monitor Drives 1 to 4.
Field bus communication data is written to and read from
the special registers of Drive 0.
Uses MEMOBUS communications.
Drive 0 sends data from its special registers to Drives 1
to 4.
Operations at the Time of Communication Error
Communication Error
Error
Codes
Operation
From controller to
communication option
bUS
Master drive
Detects bUS [Option Communication Error] and operates as specified by F6-01 [Communication Error Selection].
Slave drive
Detects CE [Modbus Communication Error] and operates as specified by H5-04 [Communication Error Stop Method].
Note:
After error detection, each drive can continue the operation specified by the last received command if the F6-01 and H5-04 settings
agree. Because the controller cannot stop the operation, you must supply a stopping method, for example an emergency stop switch.
If you set H5-05 = 0 [Comm Fault Detection Selection = Disabled], the drive will not detect CE. The H5-04 setting does not have an
effect.
From communication
option to master drive
oFAxx
Master drive
Detects oFAxx and coasts to stop.
Slave drive
Detects hLCE [High Level Communication Errors] and coasts to stop.
From master drive to
slave drive
CE
The master drive stops communicating with the slave drive in these conditions: Reset the fault to restart communication.
The slave drive detects CE after H5-09 [CE Detection Time] is expired. Then it operates in as specified with H5-04 [Communication Error
Stop Method].
A message error occurred in the send data from the slave drive 10 consecutive times.
Response from the slave drive timed out 10 consecutive times.

Table of Contents

Other manuals for YASKAWA GA500 series

Related product manuals