10 Attachment
288 YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Single-Phase 200 V Class
Model Terminal
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
B001
L/L1, N/L2 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
2.5
*2
2.5
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)
B002
L/L1, N/L2 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
2.5
*2
2.5
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)
B004
L/L1, N/L2 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2.5 2.5 6.5 M3
0.5 - 0.6
(4.4 - 5.3)
2.5
*2
2.5
*2
- M3.5
0.8 - 1.0
(7.1 - 8.9)