Loading...
10 Attachment
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction 291
Three-Phase 400 V Class
Mode
l
Terminal
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening
Torque
Nm (inlb)
Size Shape
4001
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
2.5
*2
2.5 - 6
*2
- M4
1.2 - 1.5
(10.6 - 13.3)
4002
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
2.5
*2
2.5 - 6
*2
- M4
1.2 - 1.5
(10.6 - 13.3)
4004
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2 2.5 2.5 - 4 8 M3
0.5 - 0.6
(4.4 - 5.3)
4
*2
2.5 - 6
*2
- M4
1.2 - 1.5
(10.6 - 13.3)

Other manuals for YASKAWA GA500