9
6. Support of dv1 [Z Pulse Fault] in A1-02 = 3 [Control Method Selection = Closed
Loop Vector (CLV)]
Also, when A1-02 = 3 [Control Method Selection = Closed Loop Vector (CLV)], dv1 [Z Pulse Fault], errors can now be
detected.
With Closed Loop Vector, the Z phase is not used for normal control. However, when the Z-phase pulse signal must
be used to monitor the motor position on a host controller, for example, enable this function for protection.
Added parameter
No.
(Hex.)
Name
Description
Default
(Range)
F1-16
(03AB)
Expert
Deviation 1
Detection
Selection
Sets the function to enable and disable dv1 detection.
When A1-02 = 7 [Control Method Selection = PM Closed Loop Vector
(CLV/PM)], the function is enabled at all times.
0: Disabled
1: Enabled
0
(0, 1)