11.10 n: Special Adjustment
1000 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ n6-01: Online Tuning Selection
No.
(Hex.)
Name Description
Default
(Range)
n6-01
(0570)
Online Tuning
Selection
Sets the type of motor data that Online Tuning uses for OLV control.
0
(0 - 2)
0 : Disabled
1 : Line-to-Line Resistance Tuning
The drive adjusts the motor line-to-line resistance during run. This procedure is applicable for speed values 6 Hz
and less. It also adjusts the motor resistance value to increase the overload capacity in the low speed range.
2 : Voltage Correction Tuning
The drive adjusts the output voltage during run to increase overload tolerance and minimize the effects of high
temperatures on speed precision.
Note:
Setting 2 is enabled only when b8-01 = 0 [Energy Saving Control Selection = Disabled].
■ n6-05: Online Tuning Gain
No.
(Hex.)
Name Description
Default
(Range)
n6-05
(05C7)
Expert
Online Tuning Gain
Sets the compensation gain when n6-01 = 2 [Online Tuning Selection =
Voltage Correction Tuning]. Usually it is not necessary to change this
setting.
1.0
(0.1 - 50.0)
When you use a motor that has a large secondary circuit time constant, decrease the setting value.
If the drive detects oL1 [Motor Overload], increase the setting value in 0.1-unit increments.
■ n6-11: Online Resistance Tuning
No.
(Hex.)
Name Description
Default
(Range)
n6-11
(1B56)
Expert
Online Resistance
Tuning
Sets the responsiveness for online resistor tuning. Set this parameter to
approximately 1.000 to enable the function. The function is disabled when
the value is 0.000.
0.000
(0.000 - 1.000)
◆ n7: EZ Drive
The n7 parameters provide special adjustments for EZ Vector Control.
■ n7-01: Damping Gain for Low Frequency
No.
(Hex.)
Name Description
Default
(Range)
n7-01
(3111)
Expert
Damping Gain for
Low Frequency
Sets the oscillation suppression gain for the low speed range.
1.0
(0.1 - 10.0)
Note:
• If oscillation occurs in the low speed range, increase the acceleration time or increase the setting value in 0.5-unit increments.
• To get starting torque with the setting for C4-01 [Torque Compensation Gain], decrease the setting value in 0.3-unit increments.
■ n7-05: Response Gain for Load Changes
No.
(Hex.)
Name Description
Default
(Range)
n7-05
(3115)
Expert
Response Gain for
Load Changes
Sets the response gain related to changes in the load.
100
(10 - 1000)