Parameter Details
11
11.11 o: Keypad-Related Settings
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 1011
Trend Plot Display
A - Select Ux-xx [Monitors] (Monitor
1) with o1-24.
B - Select Ux-xx [Monitors] (Monitor
2) with o1-25.
C - Set the maximum value of
Monitor 2 with o1-50
D - Set the minimum value of Monitor
2 with o1-49
E - Set the time scale with o1-51
F - Set the minimum value of Monitor
1 with o1-47
G - Set the maximum value of
Monitor 1 with o1-48
■ o1-01: User Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-01
(0500)
RUN
User Monitor
Selection
Set the U monitor for the Drive Mode. This parameter is only available
when you use an LED keypad.
106
(104 - 855)
When the drive is in Drive Mode, push on the keypad to cycle through the data in this sequence: frequency
reference → rotational direction → output frequency → output current → o1-01 selection.
Set the x-xx part of Ux-xx that is shown in the fifth position in Drive Mode. For example, to show U1-05 [Motor
Speed], set o1-01 = 105.
Note:
• You cannot select U2 monitor [Fault Trace] or U3 Monitor [Fault History].
• The monitors that you can select are different for different control methods.
■ o1-02: Monitor Selection at Power-up
No.
(Hex.)
Name Description
Default
(Range)
o1-02
(0501)
RUN
Monitor Selection at
Power-up
Sets the monitor item that the keypad screen shows after energizing the
drive. Refer to “U: Monitors” for information about the monitor items that
the keypad screen can show. This parameter is only available when using an
LED keypad.
1
(1 - 5)
1 : Frequency Reference (U1-01)
2 : Direction
3 : Output Frequency (U1-02)
4 : Output Current (U1-03)
5 : User Monitor (o1-01)
Shows the monitor item selected in o1-01 [User Monitor Selection].
■ o1-03: Frequency Display Unit Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-03
(0502)
Frequency Display
Unit Selection
Sets the display units for the frequency reference and output frequency.
Determined by A1-02
(0 - 3)