EasyManua.ls Logo

YASKAWA GA700 - Page 1015

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
11
11.11 o: Keypad-Related Settings
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 1015
The initial setup screen shows a menu where you can select the display language, set the date, time, and other
basic settings. When you set this parameter to 0, the drive will not show this screen each time you energize the
drive.
0 : No
The drive will not show the initial setup display screen each time you energize the drive. The drive will show the
Home screen.
1 : Yes
When you input the Run command before you energize the drive or when the you turn on the Run command while
the drive shows the initial setup screen, the drive will replace the initial setup screen with the Home screen.
o1-40: Home Screen Display Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-40
(11BD)
RUN
Home Screen Display
Selection
Sets the monitor display mode for the Home screen. This parameter is only
available when using an LCD keypad.
0
(0 - 3)
0 : Custom Monitor
1 : Bar Graph
2 : Analog Gauge
3 : Trend Plot
o1-41: 1st Monitor Area Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-41
(11C1)
RUN
1st Monitor Area
Selection
Sets the horizontal axis used to show the monitor that was set in o1-24
[Custom Monitor 1] as a bar graph. This parameter is only available with an
LCD keypad.
0
(0 - 2)
0 : +/- Area ( - o1-42 o1-42 )
1 : + Area ( 0 o1-42 )
2 : - Area ( - o1-42 0 )
o1-42: 1st Monitor Area Setting
No.
(Hex.)
Name Description
Default
(Range)
o1-42
(11C2)
RUN
1st Monitor Area
Setting
Sets the horizontal axis value used to display the monitor that was set in o1-
24 [Custom Monitor 1] as a bar graph. This parameter is only available with
an LCD keypad.
100.0%
(0.0 - 100.0%)
o1-43: 2nd Monitor Area Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-43
(11C3)
RUN
2nd Monitor Area
Selection
Sets the horizontal axis used to show the monitor that was set in o1-25 as a
bar graph. This parameter is only available with an LCD keypad.
0
(0 - 2)
0 : +/- Area ( - o1-44 o1-44 )
1 : + Area ( 0 o1-44 )
2 : - Area ( - o1-44 0 )
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents