11.11 o: Keypad-Related Settings
1022 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Copies the parameter setting values saved in the keypad to a different drive.
3 : Verify (check for mismatch)
Makes sure that the parameter setting values in the drive agree with the parameters saved in the keypad.
4 : Erase (backup data of keypad)
Deletes the parameter setting values saved in the keypad.
o3-02: Copy Allowed Selection
No.
(Hex.)
Name Description
Default
(Range)
o3-02
(0516)
Copy Allowed
Selection
Sets the copy function when o3-01 = 1 [Copy Keypad Function Selection =
Backup (drive keypad)].
0
(0, 1)
Note:
When you select [Parameter Backup] on the keypad menu screen to do the backup function, the drive automatically sets o3-02 = 1.
0 : Disabled
1 : Enabled
o3-04: Select Backup/Restore Location
No.
(Hex.)
Name Description
Default
(Range)
o3-04
(0B3E)
Select Backup/
Restore Location
Sets the storage location for drive parameters when you back up and restore
parameters. This parameter is only available with an LCD keypad.
0
(0 - 3)
You can use the LCD keypad to make a maximum of 4 parameter backup sets.
0 : Memory Location 1
1 : Memory Location 2
2 : Memory Location 3
3 : Memory Location 4
o3-05: Select Items to Backup/Restore
No.
(Hex.)
Name Description
Default
(Range)
o3-05
(0BDA)
Select Items to
Backup/Restore
Sets which parameters are backed up, restored, and referenced. This
parameter is only available with an LED keypad.
0
(0, 1)
0 : Standard Parameters
1 : Standard + DWEZ Parameters
Note:
The qx-xx and rx-xx parameters appear when A1-07 = 1 or 2 [DriveWorksEZ Function Selection = DWEZ Enabled or Enabled/
Disabled wDigital Input].
When o3-05 = 1, parameters are only restored and verified.
o3-06: Auto Parameter Backup Selection
No.
(Hex.)
Name Description
Default
(Range)
o3-06
(0BDE)
Auto Parameter
Backup Selection
Sets the function that automatically backs up parameters. This parameter is
only available when using an LCD keypad.
1
(0, 1)
When you connect the drive and keypad, parameters set to the drive are automatically backed up to the keypad as
specified by the setting of parameters o3-06 and o3-07.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV