11.12 T: Auto-Tuning
1038 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
T2-15: Pull-In Current Level
No.
(Hex.)
Name Description
Default
(Range)
T2-15
(0756)
Pull-In Current Level
Sets the level of the pull-in current as a percentage, where 100% = motor
rated current. Usually it is not necessary to change this setting.
30%
(0 - 120%)
If the load inertia is high, increase the setting value.
T2-16: Encoder Pulse Count (PPR)
No.
(Hex.)
Name Description
Default
(Range)
T2-16
(0738)
Encoder Pulse Count
(PPR)
Sets the number of PG (pulse generator, encoder) pulses.
1024 ppr
(1 - 15000 ppr)
Set the actual number of pulses for one full motor rotation.
T2-17: Encoder Z-Pulse Offset
No.
(Hex.)
Name Description
Default
(Range)
T2-17
(0757)
Encoder Z-Pulse
Offset
Sets the encoder Z-pulse offset (Δθ) (pulse generator, encoder) that is listed
on the motor nameplate.
0.0°
(-180.0 - +180.0°)
If you do not know the quantity of encoder (pulse generator, encoder) Z-pulse offset, or if you replaced the
encoder, do Z Pulse Offset Tuning and correct for the offset (Δθ) from the Z phase.
T3: ASR and Inertia Tuning
T3-00: Control Loop Tuning Selection
No.
(Hex.)
Name Description
Default
(Range)
T3-00
(1198)
Control Loop Tuning
Selection
Sets the type of Control Auto-Tuning.
0
(0 - 3)
0 : Inertia Tuning
1 : ASR (Speed Regulator)
2 : Deceleration Rate Tuning
3 : KEB Tuning
Note:
Settings 0 and 1 are available only when A1-02 = 3, 7 [Control Method Selection = Closed Loop Vector or PM Closed Loop Vector].
T3-01: Test Signal Frequency
No.
(Hex.)
Name Description
Default
(Range)
T3-01
(0760)
Test Signal
Frequency
Sets the frequency of the test signal applied to the motor during Inertia
Tuning. Usually it is not necessary to change this setting.
3.0 Hz
(0.1 - 20.0 Hz)
If the load inertia is too large and the drive detects a fault after Inertia Tuning, decrease the setting.
T3-02: Test Signal Amplitude
No.
(Hex.)
Name Description
Default
(Range)
T3-02
(0761)
Test Signal
Amplitude
Sets the amplitude of the test signal applied to the motor during Inertia
Tuning. Usually it is not necessary to change this setting.
0.5 rad
(0.1 - 10.0 rad)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV