EasyManua.ls Logo

YASKAWA GA700 - Improve the Power Factor; Connect an AC Reactor or a DC Reactor

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mechanical & Electrical
Installation
2
2.21 Improve the Power Factor
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 125
2.21 Improve the Power Factor
Connect an AC Reactor or a DC Reactor
AC reactors and DC reactors decrease surges in current and improve the power factor on the input side of the
drive.
Connect an AC reactor or a DC reactor to the input side (primary side) in the these conditions:
To decrease harmonic current or improve the power factor of the power supply
When there is switching of phase advancing capacitor
With a large capacity power supply transformer (600 kVA or more).
Note:
You can use an AC reactor and DC reactor together.
When you connect a thyristor converter (for example, a DC drive) to the same power supply system, you should use an AC reactor,
regardless of the conditions of the power supply.
The main circuit terminal block for the drive, and the terminal blocks for the AC and DC reactors come in different shapes. The drive
has a European-style terminal block, and the AC and DC reactors have a circular terminal block. Use caution when you prepare the
ends of the wires.
Connect an AC Reactor
Note:
When you connect an AC reactor to the output side (secondary side) of the driver, set C6-02 = 1 [Carrier Frequency Selection = 2.0
kHz].
A - Power supply
B - MCCB
C - AC reactor
D - Drive
Figure 2.126 AC Reactor Connection Example
Connect a DC Reactor
When you install a DC link choke, remove the jumper between terminals +1 and +2. If you will not use a DC link
choke, do not remove the jumper. Refer to Figure 2.127 for an example of how to wire the DC reactor.
A - Power supply
B - MCCB
C - Drive
D - DC reactor
Figure 2.127 DC Reactor Connection Example