Specifications
9
9.4 Model Specifications (400 V Class)
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 451
Table 9.6 Rating (400 V Class)
Model
Input
Voltage
Duty
Rating
4031 4038 4044 4060 4075 4089 4103
Maximum Applicable
Motor Output (kW)
< 460 V
*1
HD1 11 15 18.5 22 30 37 45
ND1 15 18.5 22 30 37 45 55
≧ 460 V
*2
HD2 11 15 18.5 22 30 37 45
ND2 15 18.5 22 30 37 45 55
Maximum Applicable
Motor Output (HP)
< 460 V
*1
HD1 15 20 25 30 40 50 60
ND1 20 25 30 40 50 60 75
≧ 460 V
*2
HD2 15 20 25 30 40 50 60
ND2 20 25 30 40 50 60 75
Input
Rated
Input
Current
(A)
*3
< 460 V
HD1 (AC) 30.6 41.3 50.5 43.1 58.3 71.5 86.5
HD1 (DC) 38 51 62 53 72 88 106
ND1 (AC) 41.3 50.5 59.7 58.3 71.5 86.5 105
ND1 (DC) 51 62 74 72 88 106 129
≥ 460 V
HD2 (AC) 25.3 34.1 41.7 35.6 48.1 59.0 71.4
HD2 (DC) 31 42 52 44 59 73 88
ND2 (AC) 34.1 41.7 49.4 48.1 59.0 71.4 86.9
ND2 (DC) 42 52 61 59 73 88 107
Outputs
Rated
Output
Capacity
(kVA)
< 460 V
*4
HD1 16 20 26 30 39 49 60
ND1 20 25 29 39 49 59 68
≧ 460 V
*5
HD2 17 22 27 32 41 52 61
ND2 22 27 32 41 52 61 76
Rated
Output
Current
(A)
< 460 V
HD1 24 31 39 45 60 75 91
ND1 31 38 44 59.6 74.9 89.2 103
≥ 460 V
HD2 21 27 34 40 52 65 77
ND2 27 34 40 52 65 77 96
Overload Tolerance
• HD: 150% of the rated output current for 60 seconds
• ND: 110% of the rated output current for 60 seconds
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
• Advanced Open Loop Vector Control (AOLV) and EZ Open Loop Vector Control
(EZOLV): 120 Hz
• Closed Loop V/f Control (CL-V/f), Closed Loop Vector Control (CLV), Advanced
Open Loop Vector Control for PM (AOLV/PM), and Closed Loop Vector Control for
PM (CLV/PM): 400 Hz
• V/f Control (V/f), Open Loop Vector Control (OLV), and Open Loop Vector Control
for PM (OLV/PM): 590 Hz
Measures
for
Harmonics
DC Reactor External options Standard internal characteristics
Braking
Device
Braking Transistor Standard internal characteristics