Specifications
9
9.4 Model Specifications (400 V Class)
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 453
Model
Input
Voltage
Duty
Rating
4140 4168 4208 4250 4296 4371 4389
Outputs
Rated
Output
Capacity
(kVA)
< 460 V
*4
HD1 74 99 118 142 171 200 244
ND1 92 111 137 165 195 244 256
≧ 460 V
*5
HD2 76 99 124 143 191 241 288
ND2 99 124 143 191 241 288 330
Rated
Output
Current
(A)
< 460 V
HD1 112 150 180 216 260 304 371
ND1 140 168 208 250 296 371 389
≥ 460 V
HD2 96 124 156 180 240 302 361
ND2 124 156 180 240 302 361 414
Overload Tolerance
• HD: 150% of the rated output current for 60 seconds
• ND: 110% of the rated output current for 60 seconds
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 5 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 10 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
• Advanced Open Loop Vector Control (AOLV) and EZ Open Loop Vector Control
(EZOLV): 120 Hz
• Closed Loop V/f Control (CL-V/f), Closed Loop Vector Control (CLV), Advanced
Open Loop Vector Control for PM (AOLV/PM), and Closed Loop Vector Control for
PM (CLV/PM): 400 Hz
• V/f Control (V/f), Open Loop Vector Control (OLV), and Open Loop Vector Control
for PM (OLV/PM): 590 Hz
Measures
for
Harmonics
DC Reactor Standard internal characteristics
Braking
Device
Braking Transistor
Standard internal
characteristics
External options
EMC
Filter
EMC Filter
IEC61800-3, C2/C3
Factory option
• Models 4xxxB: There is a category C3 EMC filter in the drive.
• Models 4xxxC: There is a category C2 EMC filter in the drive.
Power
Supply
Rated Voltage/Rated Frequency
• Three-phase AC power supply 380 V to 480 V at 50/60 Hz
• DC power supply 513 V to 679 V
Permitted Voltage Fluctuation -15% to +10%
Permitted Frequency Fluctuation ±5%
Input
Power
(kVA)
< 460 V
HD1 84 113 136 165 198 239 297
ND1 113 136 165 198 239 297 327
≥ 460 V
HD2 72 98 117 142 193 240 288
ND2 120 143 174 236 295 352 410
*1 The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2 The maximum applicable motor output complies with 460 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*3 Assumes the value at the rated output current. The input current rating changes when the power supply transformer, input reactor,
wiring connections, or power supply impedance change.
*4 The rated output capacity is calculated with a rated output voltage of 380 V.
*5 The rated output capacity is calculated with a rated output voltage of 460 V.