10.7 d: Reference Settings
520 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
d1-09
(0288)
RUN
Reference 9
Sets the frequency reference in the units from o1-03 [Frequency
Display Unit Selection].
Note:
o1-03 = 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control
Method Selection = PM Advanced Open Loop Vector, PM Closed
Loop Vector].
0.00 Hz
(0.00 - 590.00 Hz)
779
d1-10
(028B)
RUN
Reference 10
Sets the frequency reference in the units from o1-03 [Frequency
Display Unit Selection].
Note:
o1-03 = 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control
Method Selection = PM Advanced Open Loop Vector, PM Closed
Loop Vector].
0.00 Hz
(0.00 - 590.00 Hz)
780
d1-11
(028C)
RUN
Reference 11
Sets the frequency reference in the units from o1-03 [Frequency
Display Unit Selection].
Note:
o1-03 = 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control
Method Selection = PM Advanced Open Loop Vector, PM Closed
Loop Vector].
0.00 Hz
(0.00 - 590.00 Hz)
780
d1-12
(028D)
RUN
Reference 12
Sets the frequency reference in the units from o1-03 [Frequency
Display Unit Selection].
Note:
o1-03 = 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control
Method Selection = PM Advanced Open Loop Vector, PM Closed
Loop Vector].
0.00 Hz
(0.00 - 590.00 Hz)
780
d1-13
(028E)
RUN
Reference 13
Sets the frequency reference in the units from o1-03 [Frequency
Display Unit Selection].
Note:
o1-03 = 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control
Method Selection = PM Advanced Open Loop Vector, PM Closed
Loop Vector].
0.00 Hz
(0.00 - 590.00 Hz)
780
d1-14
(028F)
RUN
Reference 14
Sets the frequency reference in the units from o1-03 [Frequency
Display Unit Selection].
Note:
o1-03 = 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control
Method Selection = PM Advanced Open Loop Vector, PM Closed
Loop Vector].
0.00 Hz
(0.00 - 590.00 Hz)
781
d1-15
(0290)
RUN
Reference 15
Sets the frequency reference in the units from o1-03 [Frequency
Display Unit Selection].
Note:
o1-03 = 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control
Method Selection = PM Advanced Open Loop Vector, PM Closed
Loop Vector].
0.00 Hz
(0.00 - 590.00 Hz)
781
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV