Parameter List
10
10.10 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 551
Setting Function Description Ref.
65 KEB Ride-Thru 1
Activate (N.C.)
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
881
66 KEB Ride-Thru 1
Activate (N.O.)
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
881
67 Communications
Test Mode
Set the function for the drive to self-test RS-485 serial communications operation.
881
68 High Slip Braking
(HSB) Activate
Sets the command to use high-slip braking to stop the motor.
881
6A Drive Enable
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands
when the terminal is OFF.
881
71 Torque Control
Sets the function to switch between torque control and speed control.
ON : Torque control
OFF : Speed control
882
72 Zero Servo
Sets the function to hold a stopped motor.
882
75 Up 2 Command
Sets the function to increase the frequency reference bias value to accelerate the motor
when the terminal is activated. Set this function and H1-xx = 76 [Down 2 Command]
together.
Note:
When using this function, set the optimal bias limit value with d4-08 and d4-09 [Up/
Down 2 Bias Upper Limit/Lower Limit].
882
76 Down 2 Command
Sets the function to increase the frequency reference bias value to accelerate the motor
when the terminal is activated. Set this function and H1-xx = 75 [Up 2 Command]
together.
Note:
When using this function, set the optimal bias limit value with d4-08 and d4-09 [Up/
Down 2 Bias Upper Limit/Lower Limit].
884
77 ASR Gain (C5-03)
Select
Sets the function to switch the ASR proportional gain set in C5-01 [ASR Proportional
Gain 1] and C5-03 [ASR Proportional Gain 1/2].
ON : C5-03
OFF : C5-01
884
78 Analog TorqueRef
Polarity Invert
Sets the rotation direction of the external torque reference.
ON : External torque reference reverse direction
OFF : External torque reference forward direction
884
7A KEB Ride-Thru 2
Activate (N.C.)
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
885
7B KEB Ride-Thru 2
Activate (N.O.)
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
885
7C Short Circuit
Braking (N.O.)
Sets operation of Short Circuit Braking (N.O.).
ON : Short Circuit Braking is enabled.
OFF : Normal operation
Note:
When A1-02 = 8 [Control Method Selection = EZ Open Loop Vector Control], this
function is available if you use a PM motor.
885