Parameter List
10
10.10 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 553
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H2-06
(0437)
Watt Hour Output
Unit Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39
[MFDO Function Select = Watt Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
0
(0 - 4)
889
H2-07
(0B3A)
Modbus Register 1
Address Select
Sets the address of the MEMOBUS/Modbus register output to the
MFDO terminal.
0001
(0001 - 1FFF)
890
H2-08
(0B3B)
Modbus Register 1
Bit Select
Sets the bit of the MEMOBUS/Modbus register output to the
MFDO terminal.
0000
(0000 - FFFF)
890
H2-09
(0B3C)
Modbus Register 2
Address Select
Sets the address of the MEMOBUS/Modbus register output to the
MFDO terminal.
0001
(0001 - 1FFF)
890
H2-10
(0B3D)
Modbus Register 2
Bit Select
Sets the bit of the MEMOBUS/Modbus register output to the
MFDO terminal.
0000
(0000 - FFFF)
890
H2-20
(1540)
Comparator 1
Monitor Selection
Sets the monitor number for comparator 1. Set the x-xx part of the
Ux-xx [Monitor]. For example, set x-xx to 102 to monitor U1-02
[Output Frequency].
102
(000 - 999)
890
H2-21
(1541)
Comparator 1
Lower Limit
Sets the lower limit detection level for comparator 1 when the full
scale analog output for the monitor selected in H2-20 [Comparator
1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
891
H2-22
(1542)
Comparator 1
Upper Limit
Sets the upper limit detection level for comparator 1 when the full
scale analog output for the monitor selected in H2-20 [Comparator
1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
891
H2-23
(1543)
Comparator 1
Hysteresis
Sets the hysteresis level for comparator 1 when the full scale analog
output for the monitor selected in H2-20 [Comparator 1 Monitor
Selection] is the 100% value.
0.0%
(0.0 - 10.0%)
891
H2-24
(1544)
Comparator 1 On-
Delay Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
891
H2-25
(1545)
Comparator 1 Off-
Delay Time
Sets the off-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
891
H2-26
(1546)
Comparator 2
Monitor Selection
Sets the monitor number for comparator 2. Set the x-xx part of the
Ux-xx [Monitor]. For example, set x-xx to 102 to monitor U1-02
[Output Frequency].
103
(000 - 999)
892
H2-27
(1547)
Comparator 2
Lower Limit
Sets the lower limit detection level for comparator 1 when the full
scale analog output for the monitor selected in H2-26 [Comparator
2 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
892
H2-28
(1548)
Comparator 2
Upper Limit
Sets the upper limit detection level for comparator 1 when the full
scale analog output for the monitor selected in H2-26 [Comparator
2 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
892
H2-29
(1549)
Comparator 2
Hysteresis
Sets the hysteresis level for comparator 2 when the full scale analog
output for the monitor selected in H2-26 [Comparator 2 Monitor
Selection] is the 100% value.
0.0%
(0.0 - 10.0%)
892
H2-30
(154A)
Comparator 2 On-
Delay Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
892