Parameter List
10
10.10 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 557
Setting Function Description Ref.
E Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not turn on for CPF00 and CPF01 [Control Circuit Error] faults.
900
F Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this
setting as the PLC contact output via MEMOBUS/Modbus or the communication option.
This signal does not function if signals from the PLC are not configured.
900
10 Alarm
The terminal turns on when the drive detects a minor fault.
901
11 Fault Reset
Command Active
The terminal turns on when the drive receives the Reset command from the control
circuit terminal, serial communications, or the communication option.
901
12 Timer Output
Use this setting when the drive uses the timer function as an output terminal.
901
13 Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency
reference ± L4-04 [Speed Agree Detection Width (+/-)].
Note:
The drive uses the motor speed as the reference in CLVand CLV/PM.
ON : The output frequency is in the range of “frequency reference ± L4-04”.
OFF : The output frequency is not in the range of “frequency reference ± L4-04”.
901
14 User-Set Speed
Agree 2
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree
Detect Level (+/-)] ± L4-04 [Speed Agree Detect Width (+/-)] and in the range of the
frequency reference ± L4-04.
ON : The output frequency is in the range of “L4-03 ± L4-04” and the range of frequency
reference ± L4-04.
OFF : The output frequency is not in the range of “L4-03 ± L4-04” or the in the range of
frequency reference ± L4-04.
901
15 Frequency
Detection 3
The terminal deactivates when the output frequency is higher than the setting value of
“L4-03 [Speed Agree Detect Level (+/-)] + L4-04 [Speed Agree Detect Width (+/-)]”.
After the terminal deactivates, the terminal stays off until the output frequency is at the
value of L4-03.
Note:
• The detection level set with L4-03 is a signed value. The drive will only detect in one
direction.
• The drive uses the motor speed as the reference in CLVand CLV/PM.
ON : The output frequency is less than the value of L4-03 or is not higher than the value
of L4-03 + L4-04.
OFF : The output frequency is higher than the value of L4-03 + L4-04.
902
16 Frequency
Detection 4
The terminal activates when the output frequency is higher than the value of L4-03
[Speed Agree Detect Level (+/-)]. After the terminal activates, the terminal stays on until
the output frequency is at the value of L4-03 - L4-04.
ON : The output frequency is higher than the value of L4-03.
OFF : The output frequency is less than the value of “L4-03 - L4-04”, or it is not higher
than the value of L4-03.
902
17 Torque Detection 1
(N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-02 [Torque
Detection Level 1], or the level is less than the torque value set with L6-02 for longer
than the time set with L6-03 [Torque Detection Time 1].
903
18 Torque Detection 2
(N.O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-05 [Torque
Detection Level 2], or the level is less than the torque value set with L6-05 for longer
than the time set with L6-06 [Torque Detection Time 2].
903