Parameter Details
11
11.5 d: References
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 777
Related
Parameters
Multi-Step Speed
Reference 1
H1-xx = 3
Multi-Step Speed
Reference 2
H1-xx = 4
Multi-Step Speed
Reference 3
H1-xx = 5
Multi-Step Speed
Reference 4
H1-xx = 32
Jog Reference
Selection
H1-xx = 6
Reference 6 (d1-06) ON OFF ON OFF OFF
Reference 7 (d1-07) OFF ON ON OFF OFF
Reference 8 (d1-08) ON ON ON OFF OFF
Reference 9 (d1-09) OFF OFF OFF ON OFF
Reference 10 (d1-10) ON OFF OFF ON OFF
Reference 11 (d1-11) OFF ON OFF ON OFF
Reference 12 (d1-12) ON ON OFF ON OFF
Reference 13 (d1-13) OFF OFF ON ON OFF
Reference 14 (d1-14) ON OFF ON ON OFF
Reference 15 (d1-15) OFF ON ON ON OFF
Reference 16 (d1-16) ON ON ON ON OFF
Jog Reference (d1-
17)
*1
- - - - ON
*1 Jog Reference (JOG command) is more important than all other frequency references.
Figure 11.61 Time Chart for Multi-step Speed Reference/JOG Reference
■ d1-01: Reference 1
No.
(Hex.)
Name Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection.
0.00 Hz
(0.00 - 590.00 Hz)