11.8 H: Terminal Functions
888 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ Extend MFDO1 to MFDO3 Function Selection
You can set MFDO functions to bit 0 to bit 2 [MEMOBUS MFDO1 to 3] of MEMOBUS register 15E0 (Hex.).
Use H2-40 to H2-42 [Mbus Reg 15E0h bit0 to bit2 Output Func] to select the function.
Figure 11.88 Functional Block Diagram of MEMOBUS Multi-function Output
Table 11.66 MEMOBUS MFDO Registers
Register No.
(Hex.)
Name
15E0
bit0 MEMOBUS MFDO 1
bit1 MEMOBUS MFDO 2
bit2 MEMOBUS MFDO 3
Note:
• Refer to H2-xx “MFDO Setting Values” for more information about MFDO setting values.
• When you do not set functions to H2-40 to H2-42, set them to F.
■ Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use H2-60, H2-63, and H2-66 [Term M1-M2 Secondary Function to Term M5-M6 Secondary Function] to set the
function of the output signal for which logical operations are performed.
Use H2-61, H2-64, H2-67 [Terminal M1-M2 Logical Operation to Terminal M5-M6 Logical Operation] to set the
logical operation.
Figure 11.89 Functional Block Diagram of Logical Operation Output for MFDO 1
Table 11.67 MFDO Logical Operation Table
Logical Operation Selection
Logical Operation Expression Logical Operation Notation
H2-61, H2-64, H2-67
0 A=B=1
1 A=1 or B=1
2 A=0 or B=0
3 A=B=0
4 A=B A=B
5 A != B
6 AND(A, )
7 OR(A, )
8 - On