11.8 H: Terminal Functions
900 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ 9: Frequency Reference from Keypad
Setting Function Description
9 Frequency Reference
from Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
■ A: Run Command from Keypad
Setting Function Description
A Run Command from
Keypad
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
■ B: Torque Detection 1 (N.O.)
Setting Function Description
B Torque Detection 1
(N.O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-02 [Torque Detection
Level 1], or the level is less than the torque value set with L6-02 for longer than the time set with
L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-02 for longer than the time
set in L6-03.
• Refer to “L6: Torque Detection” for more information.
■ C: Frequency Reference Loss
Setting Function Description
C Frequency Reference
Loss
The terminal activates when the drive detects a loss of frequency reference.
Note:
Refer to “L4-05: Fref Loss Detection Selection” for more information.
■ D: Braking Resistor Fault
Setting Function Description
D Braking Resistor
Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a
braking transistor fault.
■ E: Fault
Setting Function Description
E Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not turn on for CPF00 and CPF01 [Control Circuit Error] faults.
■ F: Not Used
Setting Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as
the PLC contact output via MEMOBUS/Modbus or the communication option. This signal does not
function if signals from the PLC are not configured.